BRV Bonetti Rubinetterie Valduggia S.r.l.

MODVLVS

Regolare e distribuire energia pulita

ModvFresh Basic

Compact heat exchange unit to deliver fresh domestic hot water (DHW).

Product file

Logico

Multifunctional compact hydraulic module for the management of a direct circuit, a mixed circuit and the production of domestic hot water (DHW)

Product file

ModvBox

Modular multi-zone distribution box for wall-mounted gas boilers or heat pumps. Three types of available pump units: direct, mixed motorized, mixed fixed point.

Product file

°Caleon Thermostat - Wi-Fi

Elegant chrono-thermostat with TFT capacitive touch panel. Wi-Fi N 2.4 Ghz connection for remote control by °Caleon app.

Product file

Mixing kit for ModvFresh Basic

35÷60°C thermostatic mixing kit designed for ModvFresh Basic, with anti-scald thermostatic mixing valve for small applications.

Product file

DomvS Clima

Control unit for manifolds of heating and cooling radiant panels up to 200 m2. Fixed point thermostatic mixer or motorized rotary mixing valve. LCD room control unit.

Product file

1610

Full bore 2-way zone ball valve, with bidirectional actuator with quick connection. Dimensions from 1/2" DN15 to 1"1/4 DN32.

Product file

726 - Basic Series

Anti-scald thermostatic mixing valve for medium and small applications. Compact size. Available Kvs: 1.5, 1.8 and 3.4.

Product file

M2 MIX3 CS - DN32

2-Way pump unit for solid fuel boilers with electronic servomotor for the control of the return temperature

The unit for 1”1/4 (180 mm) circulating pumps consists of:

SUPPLY:

  • Flanged ball valve supplied with in-handle thermometer (coded red; 0°C-120°C).
  • “T” connection for mixing valve with 20 mbar non return valve (ball valve side).
  • Connection.

RETURN:

  • Connection.
  • 3-way mixing valve with electronic servomotor.
  • High efficiency synchronous pre-wired circulating pump (for the models that include it).
  • Flanged ball valve supplied with in-handle thermometer (coded blue, range 0°C-120°C).
  • Temperature sensor.

Centre distance 125 mm. EPP insulation box (Measurements: 250x400x170 mm).

PN 10, max. temperature 110°C (unit without pump).
External connections: 1”1/4 Female.

FIELD OF UTILIZATION:
For power up to 111 kW (with Δt 20 K) and maximum flow 4800 l/h.
Kvs Value: 13,0.
Approximate data calculated with a 8 m nominal lifting power circulating pump (Wilo Stratos PARA 30/1-8). For an accurate measuring or for higher flows, please refer to the curves.
Synchronous circulating pumps:
Grundfos Alpha 2L 32-60 (A6)
Wilo Stratos PARA 30/1-7 (P7)
Wilo Stratos PARA 30/1-8 (P8)

We suggest you to install two isolating valves Art. 55AMMS with nut and gasket (see Correlated Articles) after the pump unit to allow an easy service or replacement of the components of the unit.
puffer /
heating installation
solid fuel boiler
The unit, by means of a 3-way mixing valve operated by a servomotor with controller, always keeps the return temperature above the condensing temperature, preventing the deposits both in the boiler and in the flue, improving its performance and life.


The electronics of servomotor keeps constant the set temperature of the return way, monitoring it by means of a sensor (included) mounted on the pipe.
Display of the measured temperature and target temperature, on reversible LCD display.

Adjustment of target temperature adjustable from 0°C up to 99°C.
Operating range of 90°.
Power supply 230V, 2 min, torque 6 Nm. IP42.
     


Typical curves of pump unit and circulating pumps


Click to zoom

Code 1”1/4: 20555R-M3C-CT   -   with circulating pump: 20555R-M3C-(A6/P7/P8)-CT

Standard version: right supply.
Left supply version available with extra price: see price list.