BRV Bonetti Rubinetterie Valduggia S.r.l.

MODVLVS

Regolare e distribuire energia pulita

°Caleon Thermostat - Wi-Fi

Elegant chrono-thermostat with TFT capacitive touch panel. Wi-Fi N 2.4 Ghz connection for remote control by °Caleon app.

Product file

1610

Full bore 2-way zone ball valve, with bidirectional actuator with quick connection. Dimensions from 1/2" DN15 to 1"1/4 DN32.

Product file

Logico

Multifunctional compact hydraulic module for the management of a direct circuit, a mixed circuit and the production of domestic hot water (DHW)

Product file

726 - Basic Series

Anti-scald thermostatic mixing valve for medium and small applications. Compact size. Available Kvs: 1.5, 1.8 and 3.4.

Product file

DomvS Clima

Control unit for manifolds of heating and cooling radiant panels up to 200 m2. Fixed point thermostatic mixer or motorized rotary mixing valve. LCD room control unit.

Product file

Mixing kit for ModvFresh Basic

35÷60°C thermostatic mixing kit designed for ModvFresh Basic, with anti-scald thermostatic mixing valve for small applications.

Product file

ModvBox

Modular multi-zone distribution box for wall-mounted gas boilers or heat pumps. Three types of available pump units: direct, mixed motorized, mixed fixed point.

Product file

ModvFresh Basic

Compact heat exchange unit to deliver fresh domestic hot water (DHW).

Product file

M2 MIX3 - DN25

2-Way pump unit with 3-way mixing valve

The unit for 1” (180 mm) circulating pumps consists of:

SUPPLY:

  • Connection.
  • 3-way mixing valve.
  • High efficiency synchronous pre-wired circulating pump (for the models that include it).
  • Flanged ball valve supplied with in-handle thermometer (coded red, range 0°C-120°C).

RETURN:

  • Flanged ball valve with non return valve 20 mbar (which can be excluded by rotating the handle by 45°) supplied with in-handle thermometer (coded blue; 0°C-120°C).
  • “T” Connection for mixing valve.
  • Connection.

Centre distance 125 mm. EPP insulation box (Measurements: 250x380x170 mm).
PN 10, max temperature 110°C (unit without pump).
External connections:  1” Female.

FIELD OF UTILIZATION:
For power up to 35 kW (with Δt 20 K) and maximum flow 1500 l/h.
Kvs Value: 6,0.
Approximate data calculated with a 6 m nominal lifting power circulating pump.
For an accurate measuring or for higher flows, please refer to the curves shown in the technical section.
Available circulating pumps:
Wilo Yonos Para RS 25/6 (Y6)
Grundfos UPM3 Auto L 25-70 (UL7)
Wilo Yonos Para RS 25/7,5 (Y8)

We suggest you to install two isolating valves Art. 552 (see Correlated Articles) before the pump unit to allow an easy service or replacement of the components of the unit.

MODEL WITH BUILT-IN M21 SERVOMOTOR
Servomotor M21: 3 points servomotor for mixing valve. Bidirectional, reversible with fixed limit switches for an operating range of 90°. 230V, 2 min., torque: 5 Nm. IP42.
Several models available: see the section “Servomotors”.


MODEL WITH BUILT-IN AHC20 SERVOMOTOR
AHC20 servomotor: basic climatic controller with servomotor and outside sensor, with climatic regulation for mixing valve with electronic control to keep fixed the selected temperature of the room. Bidirectional, reversible with fixed limit switches for an operating range of 90°, 2 min., torque: 6 Nm. Power supply 230V. IP42.


MODEL WITH BUILT-IN CMP25-2 CLIMATIC CONTROLLER
CMP25-2 climatic controller: “touch screen” climatic controller with servomotor for mixing valve, 3 points. Bidirectional, reversible with fixed limit switches for an operating range of 90°. 230V, 2 min., torque: 10 Nm. IP42.


Versions available with reduced Kvs (using the special kits, see Correlated Articles). In the table below the resulting Kvs of the unit is shown, with the relevant maximum values of power and flowrate:

Mixing valve Kvs
Pump unit Kvs
Power Flow rate
 10,0 (standard) 6,0 (standard) 35 kW 1500 l/h
6,3 5,0 29 kW 1250 l/h
4,0 3,5 20 kW 850 l/h
2,5 2,4 14 kW 600 l/h


Measuring and check of a DN25 system

  Clicking on the icon at side it is possible to download an Excel file dealing with the measuring and the check of a DN25 pump unit; it is possible to select the model and the working parameters, so getting a check of the power and of the residual lifting power.In case of underfloor heating system the surface that can be managed is approximately calculated. Changing the starting data it is possible to simulate different employment situations and to make your considerations.

M2 MIX3:
Code 1”: 20355R-M3 - with circ. pump: 20355R-M3-(Y6/UL7/Y8)

M2 MIX3 with built-in M21 servomotor:
Code 1”: 20355R-M3-M21 - with circ. pump: 20355R-M3-(Y6/U7/Y8)-M21

M2 MIX3 with built-in AHC20 servomotor:
Code 1”: 20355R-M3-AHC - with circ. pump: 20355R-M3-(Y6/U7/Y8)-AHC

M2 MIX3 with built-in CMP25-2 climatic controller:
Code 1”: 20355R-M3-CMP - with circ. pump: 20355R-M3-(Y6/U7/Y8)-CMP

Note: in units with pre-assembled pump, the pump
Grundfos UPM3 AUTO L 25-70 is identified in the code with U7.


Standard version: right supply.
Left supply version available with extra price: see price list.