BRV Bonetti Rubinetterie Valduggia S.r.l.

MODVLVS

Regolare e distribuire energia pulita

T10H

Thermostatic control head with liquid gas sensor, compatible M30x1,5. EN 215 approved, TELL certification.

Product file

RCD2

Remote control of the heating system for AHC40 and CMP25-2 climatic controllers. Automatic pairing with climatic controller.

Product file

M2 MIX3 FIX - DN25

2-Way pump unit with 3-way mixing valve with electronic servomotor for the constant temperature. Heating and Cooling.

Product file

514

Ball valve with filter in hot forged brass. To fill the installation. The filter can be easily removed, to be cleaned and inspected. Nickel plated.

Product file

Solo 2

Pump unit for stratified loading to supply the heat produced by a solar thermal installation. Equipped with pre-programmed controller and Class A circulating pumps.

Product file

Logico

Multifunctional compact hydraulic module for the management of a direct circuit, a mixed circuit and the production of domestic hot water (DHW)

Product file

M2 FIX3 CS - DN20

2-Way pump unit with recycling thermic valve for solid fuel boilers. High efficiency circulating pumps. Start opening temperature 60°C, 45°C or 55°C.

Product file

CLIMA L - DN25

2-way pump unit with 3-way mixing valve and electronic circulating pump. Built-in Clima L 24VDC climatic controller for complex installations

Product file

1055

3-way motorizable rotating mixing valve for heating, cooling and solar thermal installations. Working as mixer or diverter. Kvs from 2,5 up to 25.

Product file

Kascata

System to connect on cascade several HDW pump units ModvFresh, to obtain flows up to 200 l/min and powers up to 500 kW. Anti-Legionnaire function to avoid bacterial pollution.

Product file

DomvS Circ 1

Hot domestic water recycling kit for storage tanks with coils. 35÷60°C. Available version provided circulating pump with temperature sensor and timer. Available Kvs: 2,5 and 4,0.

Product file

687 MIX

Very small size adjustment kit for distribution box, with motorizable 3-way rotating mixing valve. High efficiency circulating pump.

Product file

789R

High performance thermostatic diverting valve. Adjustable temperature from 38°C up to 54°C. Kvs 2,5 towards the gate, 3,5 towards the gate 2.

Product file

ModvFresh 1

Pump unit to deliver fresh HDW with thermostatic controller, flow rate up to 20 l/min or 40 l/min. Possibility to make a parallel connection of up to 5 units for power up to 500 kW.

Product file

1066

4-way motorizable rotating mixing valve for heating, cooling and solar thermal installations. Kvs from 2,5 up to 25.

Product file

MCCS 745

Anti-condensing recycling and distribution pump unit with thermostatic control of the return temperature to the solid fuel heating sources.

Product file

°Caleon

Stylish room controller for easy remote control of the heating system. For Weather-Compensated Heating Controllers 24 VDC MHCC and LHCC.

Product file

ModvFresh 1

Pump unit to deliver fresh hot domestic water (HDW) with thermostatic controller and high efficiency pump
Employment: on the inertial cylinders or similar, connected to solar thermal installations, wood, pellets, biomass boilers etc. when the stratification is not a primary requirement.
It provides fresh hot domestic water, avoiding phenomena of bacterial pollution, such as the legionnaire’s disease etc., made by the stagnation of the hot water.
ModvFresh 1 is provided with a weld-braised plate heat exchanger made in stainless steel AISI 316 and with a thermostatic mixer adjustable from 45 up to 70 °C.

Two models are available, fully assembled and pre-wired:
  • 50 kW, with variable flow up to 20 l/min, for domestic use installations;
  • 100 kW, with variable flow up to 40 l/min, for small commercial installations;
with the followings specifications:
  • Very low headlosses. The circulating pump starts to run at flows less than 1 l/min thanks to a differential manostat;
  • No electric wirings are requested: the unit is pre-wired and shop tested;
  • Easy temperature adjustment, by means of the graduated knob of the MultiMix thermostatic mixer;
  • The heat exchanger can be easily removed in case of maintenance and/of cleaning;
  • PPE insulation box (398 x 500 x 207 mm). A special back plate fixes the unit to the insulation box and it allows a quick fitting to the wall or to the solar cylinder;
  • The pump unit is supplied with 3/4” Male connections (pipe-union).
A special ball valves kit, on request (to be ordered), completes the installation.
FIELD OF UTILIZATION:
For a maximum power of 100 kW and flow up to 40 l/min.
Nominal supply temperature of the storage tank: 60 °C.
Nominal temperature of the water supply: 10 °C.
Nominal temperature of HDW production 45 °C, adjustable up to 70 °C.


 
Technical features

Max allowed pressure: 6 bar

Working temperature:
2 ÷ 95 °C

Setting accuracy of Multimix
Mixing Valve (model 50 kW):
±1°C
(Kvs 2,5)

Setting accuracy of Multimix
Mixing Valve (model 100 kW):
±2°C
(Kvs 4,0)

Headloss in the secondary circuit at the flow of 20 l/min
(model 50 kW):
3 mH2O

Headloss in the secondary circuit at the flow of 40 l/min

(model 100 kW)
:
9 mH2O

Minimum diameter size of the pipes: DN20 (Cu 22x1).


Hydraulic scheme


(1) Circulating pump (4) Differential manostat
(2) Plate heat exchanger (5) Check valve
(3) Thermostatic mixing valve    
Unit assembled with optional ball valves kit

Calculation of the performances of the pump unit

  Click on the icon here at side and download an Excel file dedicated to the calculation of the performances of ModvFresh pump units. Starting from the installation data and taking into consideration the diagrams of the following section the supplied power, the supply time, the overall flow and the re-establishment time of the storage tank temperature are calculated. Changing the starting data you can simulate various and different utilization situations and do your remarks.

Diagrams of the pump unit performances

The following diagrams relate the user’s flow rate and the supply temperature to the buffer storage tank, according to the requested temperature of HDW. This allows to identify the minimum supply temperature needed to supply HDW at a required temperature and flow. Vice versa it is also possible to fix which is the maximum usable flow at the selected HDW temperature, at the available supply temperature.

HDW pump unit ModvFresh 1 - 50 kW







  

HDW pump unit ModvFresh 1 - 100 kW







 
The buffer temperature must be almost 5 K higher than the desired temperature of the domestic water. Bigger temperature differences allow to extend the tapping time.

Return temperature to the storage tank

The return temperature to the storage tank is variable and it depends on the temperature and flow conditions. For instance if the supply temperature of the storage tank is high, the return temperature, after the thermic exchange into the heat exchanger, will be consequently and proportionally high. This fact is enlarged with small user’s flows (small heat exchange) and it decreases with big user flows (high heat exchange). Therefore, if you do not want to destroy the stratification of the storage tank, we suggest to install a thermic valve on the return line to the storage tank to “charge” the tank at different levels at the requested temperature.

ModvFresh 1 parallel connection

If high flows and powers are requested it is possible to make a parallel connection of up to five ModvFresh 1 (100 kW model) to supply up to 200 l/min and a nominal power of 500 kW without installing any other device such as electronic controllers, motorized valves, flow sensors, etc.



The connecting scheme is particularly suitable for installations where the request of flow from the user is nearly constant, this to optimize the power consumption of the circulating pumps that are all activated at a very small flow; the control of the temperature is anyway assured during the whole use of the flow.

n the following file the main working parameters of the ModvFresh 1 on parallel connection are shown (the data have been obtained at a cold water inlet temperature of 10 °C). For an accurate measuring, please contact our Technical Department.

ModvFresh 1 100 kWpump unit to deliver HDW: installation on parallel connection
Requested flow [l/min] Number of
ModvFresh 1,
100 kW
Hot water selected temperature [°C] Supply required temp.  (storage tank) [°C] Supplied power [kW] Minimum diameter
of the pipes [mm]
80 2 50 70 224 28x1,5
120 3 50 70 336 35x1,5
160 4 50 70 448 35x1,5
200 5 50 70 560 42x1,5


FIELD OF UTILIZATION:
For a maximum nominal power of 500 kW and flow up to 200 l/min;
Nominal supply temperature of the storage tank: 60 °C;
Nominal temperature of the water supply: 10 °C;
Nominal temperature of HDW production 45 °C, adjustable up to 70 °C;
Temperature stability ±4 °C;
Return temperature to the storage tank: see specific section.
Code 50 kW, 3/4”: 031100-50-20
Code 100 kW, 3/4”: 031100-100-40